Problems for independent solution



Problem 5. Calculate a system of artificial earthing for electric sets at an airport. Determine the object of earthing by the standard of earthing rn=4W. The input data are adduced in tab. 3.3; 3.4. The number of version is determined by two last digits in the test book. For example, version 38, we take input data from tab. 3.3 and column 3, and from tab, 3.4 from the column 8.

4.1. Hints to the problem 5. 4.1.1.Resistance of a soil

r=rmKs

where rm -the resistance of soil measured, taken from tab. 3. 19 Ks -factor of seasonal prevalence - from tab. 3.3.

5.1.2 We find the resistance of a single earthing electrode, the number of earthing electrodes, operating ratios of a single earthing electrode and strip (tab. 3.2 and items 4.1, 4.2, 4.3 of present practical lesson).

 


3.4.10. Опір штучного контурного заземлення Rк.з. = 0,72 Ом менший від необхідного Rшт = 0,75 Ом і тому приймають розра- хований контур заземлення.

Опір контурного групового заземлення підстанції з урахуванням природного заземлення складе:

Опір Rг.к.з. = 0,486 Ом менший від Rн = 0,5 Ом, отже, розрахований контур штучного заземлення задовольняє умову задачі.

3.4.11.Потенціал контурного заземлення в аварійний період складе:

jАВ = Iз × Rг.к.з..= 4500 × 0,486 = 2187 В

Такий потенціал є допустимим, тому що він менший від і 10000 В.

4. Задача для самостійного розв'язування

Задача 5. Розрахувати систему штучного заземлення елект-роустановок в аеропорту. Визначити об'єкт (за нормою, заземлення rн) заземлення. Вихідні дані наведено в табл. 3.3 і 3.4. Номер варіанта визначається за двома останніми цифрами залікової книжки. Наприклад, варіант 38: вихідні дані треба взяти з табл. 3.3 (графа 3) і табл. 3.4 (графа 8).

4.1. Вказівки до розв'язування задачі 5

4.1.1. Питомий опір ґрунту визначають за табл. 3.1 і розраховують за формулою

r = rвим Кс,

де rвим - питомий опір ґрунту виміряний (табл. 3.1); Ксез - коефіцієнт сезонності (табл. 3.3).

5.1.2. Визначають опір одиночного заземлювача, кількість заземлювачів, коефіцієнти використання одиночного заземлювача і смуги (за табл. 3.2 і вказівками 4.1 - 4.3).


Table 3.3

Input data for problem 5

Values for The first variants №
Soil Sand S-sand Black earth Loam Clay Peat Fresh water Sea water Sand S-sand
Increasing Coef. of speci-fic soil resistance factor of seasonal prevalence Ks 2.0 1.5 1.5 1.6 1.1 1.8 2.2 2.1 1.1 1.9

 

Table 3.4

Input data for problem 5

 

Elements for earthing, and their dimensions The second variants №
Steel earting rods: length l, m 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9
diameter d, m 0.02 0.032 0.038 0.050 0.038 0.025 0.038 0.038 0.025 0.050
Depth of burying H, m 1.8 2.0 1.8 1.9 2.0 2.2 2.3 2.1 2.2 2.3
Steel strip b, m 0.04 0.04 0.10 0.04 0.10 0.04 0.10 0.04 0.04 0.10
Standard resistance of an earthing mat rn, W 0.5 0.5

 


Таблиця 3.3

Вихідні дані для розв'язування задачі 5

Дані для розрахунку     Перша цифра номера варіанта
5
Ґрунт Пісок Супісок Чорнозем Суглинок Глина Торф Вода річкова Вода морська Пісок Супісок
Коефіцієнт збільшення питомого опору ґрунту (коефіцієнт сезонності Ксез) 2,0 1,5 1,5 1,6 1,1 1,8 2,2 2,1 1,1 1,9

Таблиця 3.4

Вихідні дані для розв'язування задачі 5

Елементи заземлення їхні розміри, м Друга цифра номера варіантів
Заземлювачі - сталеві стрижні: довжина l, м 2,0 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9
діаметр d, м 0,02 0,032 0,038 0,050 0,038 0,025 0,038 0,038 0,025 0,050
Глибина закладення H, м 1,8 2,0 1,8 1,9 2,0 2,2 2,3 2,1 2,2 2,3
Ширина смугової сталі Ь, м 0,04 0,04 0,10 0,04 0,10 0,04 0,10 0,04 0,04 0,10
Норми rн, Ом 0,5 0,5

Problem 6. Calculate the value of step voltage, which one can affect a person at the distance of x = 1,0; 1,5; 2,0; 2,5; 3,0; 3,5; 4,0; 4,5; 5,0; 5,5 m from a place of current fault ground. The fault to ground current Ife = 100; 105; 110; 115; 120; 125; 125; 130; 135; 140; 145 A. The value of a step a = 0,8 m, soil resistance p=1000W×m.

Hints to the problem 6

4.2.1. Learn for the solution of the problem [2, p. 160-168]; [4, p. 26-29]; [5, p. 183-185].

4.2.2. Use one value of x and Ifefrom adduced in the problem

for versions of the problem. The value of p is identical to all of ten versions.

 

It is necessary to understand:

1. Measures of electrical safety determination in ГОСТ 12.1.019-79 and ПУЕ-86.

2. It is necessary to choose the electrical equipment for fire-safe areas and apartments for ГОСТ 12.2.020-76.

 

It is necessary to memorize:

1. Four subsections in a project document of the question of guard of work - list of production factors dangerous and harmful at the technical document of object which is designed; technical, that turn off or limit influence on the personnel of production factors dangerous and harmful; providing of fire safety of object; instructions on the guard of work.



 


Задача 6. Визначити значення крокової напруги, що може впливати на людину на відстані х = 1,0; 1,5; 2,0; 2,5; 3,0; 3,5; 4,0; 4,5; 5,0; 5,5 м від місця замикання електричного струму на землю. Струм замикання на землю Iз = 100; 105; 110; 115; 120; 125; 125; 130; 135; 140; 145 А. Значення кроку а = 0,8 м, питомий опір ґрунту ρ = 1000 Ом • м.

4.2. Вказівки до розв'язування задачі 6

4.2.1, Для розв'язування задачі необхідно вивчити матеріал за літературою [2, с. 160-168]; [4, с. 26-29]; [5, с. 183-185].

4.2.2. Для варіантів задачі треба використовувати по одному значенню х,м і Iз, А з наведених у задачі. Значення ρ для всіх десятьох варіантів однакове.

 

Необхідно зрозуміти:

 

1. Заходи електробезпеки визначенні у ГОСТ 12.1.019-79 та ПУЕ-86.

2. Електроустаткування для вибухо-пожежонебезпеч-них зон і приміщень слід вибирати по ГОСТ 12.2.020-76.

 

Слід запам’ятати:

1.Чотири підрозділи у проектної документації по питанням охорони праці – перелік небезпечних і шкідливих виробничих факторів при технічній документації об’єкта, що проектується; технічні, що виключають або обмежують вплив на персонал небезпечних і шкідливих виробничих факторів; забезпечення пожежної безпеки об’єкта; інструкції з охорони праці.

 

2. Requirements of fire safety certain in ГОСТ 12.1.004-91, explosive - in ГОСТ 12.1.010-76.

It is necessary to be able:

To choose explosion-protected electrical equipment of the promoted reliability against the explosion in which explosion protection is provided only in the set mode of his operations, with some type of explosion protection.

 

Questionnaire

1. What basic subsections on labour precaution does the design documentation contain?

2. Name 10 hazards under facilities & installation operation.

3. Name 10 hazards under any facilities & installation operation.

4. What rates of resistance of equipment protective earthing do you know?

5. Requirements to fire prevention system in accordance with all-Union State Standard 12.1.004-91.

6. Requirements to fire protection system in accordance with all-Union State Standard 12.1.004-91.

7. Define the basic fire protection measures of any equipment at your option.

8. How is the electric equipment subdivided depending on an implosion protection level?

9. What kinds of explosion-proof of electrical equipment are known for you?

10. Name subdivisions of instructions on a labour precaution.

11. What does each subdivision of the instruction contain?

12. How is it necessary to state materials of the instruction?

 

 

2.Вимоги пожежної безпеки визначені у ГОСТ 12.1.004-91, вибухової - у ГОСТ 12.1.010-76.

 

Треба вміти:

Вибрати вибухозахищене енергоустаткування підвищеної надійності проти вибуху, в якому вибухозахист забезпечується тільки у встановленому режимі його роботи, з деяким видом вибухозахисту.

 

Контрольні запитання

 

1. Які основні підрозділи з охорони праці містить проектна документація?

2. Назвіть 10 небезпечних виробничих факторів при експлуатації устаткування, установки.

3. Назвіть 10 шкідливих виробничих факторів при експлуатації якого-небудь промислового устаткування, установки.

4. Які норми опору захисного заземлення устаткування Ви знаєте?

5. Вимоги до системи запобігання пожежі за ГОСТ 12.1.004-91.

6. Вимоги до системи протипожежного захисту за ГОСТ 12.1.004-91.

7. Визначте основні міри пожежного захисту якого-небудь устаткування на Ваш розсуд.

8. Як розділяється електроустаткування в залежності від рівня вибухозахисту?

9. Які види вибухозахисту електроустаткування Вам відомі?

10. Назвіть розділи інструкцій з охорони праці.

11. Що містить кожен розділ інструкції?

12. Як слід викладати матеріали інструкції?

 

 